44 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Inputs
18.01.2012
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Adjustable values / remarks
N.X1
Activation of function by assigning one of these
identifier to the input:
Outside air temperature, °C, %, g/kg, kJ/kg, W/m²,
m/s, bar, mbar, Pa, ppm,
universal 000.0, universal 0000, digital, pulse.
...
Ditto
RMZ787(2).X4
Ditto
The settings made here are also displayed under:
"Main menu > Device information > Extra configuration > Input identifier"
•
The unit of the outside temperature is always °C or °F.
•
The outside air temperature can also be sent via bus (KNX), see Sec. 7.5
•
The units °C, %, g/kg, kJ/kg, W/m², m/s, bar, mbar, Pa, ppm, 100 and 1000 are
always analog inputs
•
Digital inputs are without units.
Logical display for signal handling: 0 = off, 1 = on.
7.1.3
Cause
Cause displays the source of an input value. The following types are available:
•
Terminal: Used as local terminal
•
LTE mode: Used as LTE transmission and reception objects
•
S-mode: Used as S-mode object
•
Simulation: Input terminal simulation
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > ...X...
Operating line
Range
Factory setting
Cause
Terminal, LTE mode, S-
mode, Simulation
The LTE transmission and reception objects are described in Section 13.2.4.
7.1.4
Input terminal simulation
Each input terminal can be simulated to test plant reaction.
Main menu > Inputs > Simulation inputs >
Operating line
Range
(depends on type)
Factory setting
(by type)
N.X1…
A8 (2).X4
----,
−
50...
+
50 °C
----
Only authorized staff may override inputs within a limited period of time!
The fault message "Simulation inputs active" is sent during terminal simulation.
Configuration
Notes
Note
Setting values