Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Communication
18.01.2012
A RMB795B logic output wants a second device to be made available as release
command. A release command generated in device 1 is sent as transmission
object via a digital output. Device 2 uses this command to start the rooftop fan.
In the reverse direction, any operating message in device 2 is sent as a
transmission via a digital output to device 1, where it is processes accordingly.
The following transmission and reception zones are engineered for example tasks:
RMU7x0B, device 1
RMS705B, device 2
Value
Terminal Transmission
zone
Terminal Reception
zones
N.Q1
1
N.X1 1
Release
rooftop
fan
Terminal Reception
zones
Terminal Transmission
zone
N.X1
2
N.Q2 2
Operating
message rooftop
fan
= Transmit
= Receive
In RMS705B, device 1, the following is configured:
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Range
Factory setting
N.X1 Digital
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
Range
Factory setting
N.Q1 1
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
Range
Factory setting
N.X1 2
Example 2
Data exchange concept
Configuration
Device 1