Main menu > Commissioning > Wiring test > Outputs
Operating line
Comments
Refrigeration demand
relay
---, 0...100 % (relay switches >= 1 %).
Refrigeration demand
modulating
---, 0...100 %
11.6 Function block "H/C changeover"
11.6.1 Use and functions
The function block heating/cooling changeover is used to changeover the operating
mode (heating or cooling) in 2-pipe systems.
The preselection heating/cooling can be generated on the device or received as
signal heating/cooling from the bus.
23
H / C changeover
The following types of changeover are available for operating mode preselection
H/C:
•
Changeover with operating mode selector via operation.
•
Changeover with analog input (e. g. for changeover by outside temperature or
by flow temperature).
•
Changeover with digital input (e.g. to change over via manual switch or via
changeover thermostat in the flow).
•
Changeover by date.
If several changeover types are active, the operating mode is determined by the
following priority selection:
1. Operating mode selector
2. H/C changeover input
3. Heating/cooling by calendar
The preselection operating mode heating/cooling is provided to the heat
distribution zone and refrigeration distribution zone to all other controllers in the
same zone.
In a hydraulic circuit, the operating mode heating/cooling can be preselected only
via one point. If several changeover signals are sent simultaneously to the bus
within the same distribution zone, a fault message is generated.
The preselected operating mode input H/C should be activated at the precontroller
or generator where possible.
When the function block has been activated and a "H/C changeover input" has
been defined, the RMB795B central control unit can pass on via bus the external
changeover signal received via a digital input Xx to the RXB/RXL room controllers.
Setting values
Application
Recommendation
Function