19.3 C3127_Planning and commissioning
protocol
To ensure successful planning of KNX communication between the RMB795B
central control unit and the RXB/RXL room controllers or RDG/RDF/RDU room
thermostats, a Planning and Commissioning Report has been made available. It is
used to straightforwardly list and document all settings required for communication.
The file name is: C3127_IBN-Protokoll_Komm.xls
The following illustration shows part of a report (application example Sport Ltd):
Planning and Commissioning Report, Communication Synco 700
Possible settings
RMU RMH RMK OZW RMB RXB QAW
1
2
3
4
5
6
7
8
9
0
Plant
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Room number
309
307
308
308
308
Device name
X
X
X
-
X
X
-
Reception
Conference Reception
Office
Office
Office
Office
Device type
RMU
7..
RMH,
RMZ
RMK
OZW
771...
RMB
795
RXB
....
QAW
740
RMB795
RXB..
RMB795 [2] RXB..
RXB..
RXB..
RXB..
Plant type
X
X
X
-
X
X
-
B
FC03
FC03
FC03
FC03
FC03
KNX-ID (Example ID: 00FD000016D5)
X
X
X
X
X
X
X
Area [ 0...15 ] . Line [ 1; 2...15 ] .
Device address [1..253;
255
]
X
X
X
X
X
X
X
0.2.10
0.2.114
0.2.110
0.2.111
0.2.112
0.2.113
Decentral bus power supply [ Off,
On
]
X
X
X
-
X
-
-
Aus
Clock time operation [
Autonomous
, Slave, Master ]
X
X
X
X
X
-
-
Autonom
Remote setting chlock slave [ No,
Yes
]
X
X
X
X
X
-
-
Nein
Remote reset of fault [
No
, Yes ]
X
X
X
-
X
-
-
Nein
Geographical zone (Apartment.Room.Subzone)
(A.R.S) [
1
...126 ].[ 1...63 ]. [1]
X
2
2X
X
-
10X X.X.1
X
1.1.1
1.1.1
2.1.1
2.1.1
2.2.1
2.3.1
2.4.1
(with own room sensor)
X
1
2X
X
-
-
X
X
X
----
X
X
X
Time switch operation [
Autonomous
, Slave, Master ]
X
1
2X
X
-
-
-
-
Time switch slave (apartment) [
1
...126 ] . 1 . 1
X
1
2X
X
-
-
X.1.1
-
1.1.1
2.1.1
2.1.1
2.1.1
2.1.1
Temperature control [
Master
, Slave ]
-
-
-
-
-
X
-
Master
Master
Master
Master
Master
* Control strategy [
Caskade
, Constant, Alternating ]
X
4
-
-
-
-
-
-
** Combination of room control [
Master
,
Slave external setpoint , Slave internal setpoint ]
-
2X
X
-
-
-
-
Room group (name)
-
-
-
-
10X
-
-
Conference
Office
QAW operation zone (apartment) [ ---,
1
...126 ] . 1 . 1
-
-
-
-
10X
-
-
DHW zone [
1
...31 ]
-
X
-
-
-
-
-
Time switch operation [
Autonomous
, Slave, Master ]
-
X
-
-
-
-
-
Time switch slave, from BW zone [
1
...31 ]
-
X
-
-
-
-
-
Holidays / secial day operation [
Autonom
, Slave, Master ]
X
1
X
X
-
10X
-
-
Holiday / special day zone [
1
...31 ]
X
1
X
X
-
10X
-
-
Outside temperature zone [
----
, 1...31 ]
X
X
X
-
X
-
-
(with own sensor)
X
X
X
-
X
-
-
Heat distribution zone source side [ ----,
1
...31 ]
X
1
X
5
-
-
X
X
-
Heat distribution zone consumer side [ 1...31 ]
X
3
X
6
-
-
X
-
-
Refrigation distr zone source side [ ----, 1...31 ]
X
2
-
-
-
X
X
-
Refrigeration zone consumer side [
1
...31 ]
X
3
-
-
-
X
-
-
Heat distribution zone main distributor [
1
...31 ]
-
-
X
-
-
-
-
Heat distribution zone prim controller [ 1,
2
...31 ]
-
-
X
-
-
-
-
Solar zone [
----
, 1...31 ]
-
X
-
-
-
-
-
(with own sensor)
-
X
-
-
-
-
-
Wind zone [
----
, 1...31 ]
-
X
-
-
-
-
-
(with own sensor)
-
X
-
-
-
-
-
Generation zone Boiler sequence zone [ ----,
1
…16 ]
-
-
X
-
-
-
Legend:
* Commissioning > Settings >
X
5
Basic type 0-x, 1-x, 2-x
Object
Controller 1 > Cascade controller > Control strategy
X
6
Basic type 1-x, 2-x, 3-x, 4-x
X
1
Basic type A, U
Planner
Date
** Commissioning > Extra configuration
X
2
Basic type A, C, U
Heating circuit 1/2 >Functions>Room control combination> X
3
Basic type C
X
4
Basic type A
Holidays /
Special days
Distribution zone
Information
Room /
Room group
Basic settings
Domestic hot
water
Date
Commissioner
Menu
Purpose
Examples