Configuration and operation
4.9 Access to the Web server
CP 1243-8 IRC
96
Operating Instructions, 06/2015, C79000-G8976-C385-01
4.9
Access to the Web server
Access to the Web server of the CPU
The Web server of the S7-1200 station is located in the CPU. Via the LAN interface of the
CP, you have access to the Web server of the CPU.
Access using HTTPS: When there is secure access (HTTPS) to the Web server using the IP
address of the CP, the SSL certificate of the CPU is displayed.
4.10
Time stamp
Time stamp
The values of the data points are transferred by the CP with a time stamp. The time stamp is
coded in 2 double words. The exception is the half byte (nibble) with the time status.
The two double words have the following assignment:
Table 4- 6
Assignment of the two double words
Name of the double word Byte no. Content
High nibble
Low nibble
RecTimeStamp_1
0
Year * 10
Year * 1
1
Month * 10
Month * 1
2
Day * 10
Day * 1
3
Hour * 10
Hour * 1
RecTimeStamp_2
0
Minute * 10
Minute * 1
1
Second * 10
Second * 1
2
Millisecond * 100
Millisecond * 10
3
Millisecond * 1
Time status
Table 4- 7
The assignment of the half byte with the time status (low nibble of byte 3 of Rec-
TimeStamp_2)
Bit No.
Value
Meaning
0
0
Time is invalid
1
Time is valid
1
0
Standard time
1
Daylight saving time
2
Not used
3
Not used
Содержание CP 1243-8 IRC
Страница 10: ...Table of contents CP 1243 8 IRC 10 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 104: ...Diagnostics and upkeep 6 3 Module replacement CP 1243 8 IRC 104 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 112: ...Approvals CP 1243 8 IRC 112 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 114: ...Dimension drawings CP 1243 8 IRC 114 Operating Instructions 06 2015 C79000 G8976 C385 01 Figure B 2 From above ...
Страница 134: ...Accessories C 4 Connecting cables CP 1243 8 IRC 134 Operating Instructions 06 2015 C79000 G8976 C385 01 ...