Configuration and operation
4.7 Configuration in STEP 7 Basic
CP 1243-8 IRC
80
Operating Instructions, 06/2015, C79000-G8976-C385-01
The 500 millisecond cycle is started by the integrative threshold value calculation. In this
cycle, the values are saved even when the following preprocessing options are enabled:
●
Unipolar transfer
●
Fault suppression time
●
Limit value calculation
●
Smoothing
Mean value generation
Note
Restricted preprocessing options if mean value generation is configured
If you configure mean value generation for an analog value event, the following
preprocessing options are not available:
•
Unipolar transfer
•
Fault suppression time
•
Smoothing
Function
With this parameter, acquired analog values are transferred as mean values.
If mean value generation is active, it makes sense to configure a time trigger..
The current values of an analog data point are read in a 100 millisecond cycle and totaled.
The number of read values per time unit depends on the read cycle of the CPU and the CPU
scan cycle of the CP.
The mean value is calculated from the accumulated values as soon as the transfer is
triggered by a trigger. Following this, the accumulation starts again so that the next mean
value can be calculated.
The mean value can also be calculated if the transmission of the analog value message is
triggered by a request from the communications partner. The duration of the mean value
calculation period is then the time from the last transmission (for example triggered by the
trigger) to the time of the request. Once again, the accumulation restarts so that the next
mean value can be calculated.
Input modules: Overflow range / underflow range
As soon as a value is acquired in the overflow or underflow range, mean value generation is
stopped. The value 32767 / 7FFF
h
or -32768 / 8000
h
is saved as an invalid mean value for
the current mean value calculation period and sent with the next message.
Содержание CP 1243-8 IRC
Страница 10: ...Table of contents CP 1243 8 IRC 10 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 104: ...Diagnostics and upkeep 6 3 Module replacement CP 1243 8 IRC 104 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 112: ...Approvals CP 1243 8 IRC 112 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 114: ...Dimension drawings CP 1243 8 IRC 114 Operating Instructions 06 2015 C79000 G8976 C385 01 Figure B 2 From above ...
Страница 134: ...Accessories C 4 Connecting cables CP 1243 8 IRC 134 Operating Instructions 06 2015 C79000 G8976 C385 01 ...