Configuration and operation
4.7 Configuration in STEP 7 Basic
CP 1243-8 IRC
78
Operating Instructions, 06/2015, C79000-G8976-C385-01
●
At the time 6.0 s: The value of the integrated deviation is at 2.1. The new process value
stored in the send buffer is 19.9.
In this example, if a deviation of the process value of approximately 0.5 should fire the
trigger, then with the behavior of the process value shown here a threshold value of
approximately 1.5 ... 2.5 would need to be configured.
4.7.16
Analog value preprocessing
CPs with data point configuration support analog value preprocessing. For analog value data
points, some or all of the functions described below can be configured.
Requirements and restrictions
You will find the requirements for the configuration of the preprocessing options and
restrictions in the section relating to the particular function.
Note
Restrictions due to configured triggers
The analog value preprocessing options "Fault suppression time", "Limit value calculation"
and "smoothing" are not performed if no threshold value trigger is configured for the relevant
data point.. In these cases, the read process value of the data point is entered in the image
memory of the CP before the preprocessing cycle of the threshold value calculation (500 ms)
elapses.
The analog value preprocessing options "Fault suppression time", "Limit value check" and
"smoothing" are not performed if no threshold value trigger is configured for the relevant data
point.. In these cases, the read process value of the data point is entered in the image
memory of the CP before the preprocessing cycle of the threshold value calculation (500 ms)
elapses.
Содержание CP 1243-8 IRC
Страница 10: ...Table of contents CP 1243 8 IRC 10 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 104: ...Diagnostics and upkeep 6 3 Module replacement CP 1243 8 IRC 104 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 112: ...Approvals CP 1243 8 IRC 112 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 114: ...Dimension drawings CP 1243 8 IRC 114 Operating Instructions 06 2015 C79000 G8976 C385 01 Figure B 2 From above ...
Страница 134: ...Accessories C 4 Connecting cables CP 1243 8 IRC 134 Operating Instructions 06 2015 C79000 G8976 C385 01 ...