Configuration and operation
4.7 Configuration in STEP 7 Basic
CP 1243-8 IRC
Operating Instructions, 06/2015, C79000-G8976-C385-01
71
1: Mirroring back
The mirroring back function using the "Value monitoring" parameter can be configured for
the following data point types:
●
Setpoint Output
●
Parameter Output
The local values of the data points of this type can be monitored for change and the changes
transferred to the master with the Value monitoring function.
Changing a local value can, for example, be caused by manual operator input on site.
To allow the value resulting from local events or interventions to be transferred to the master
station, a mirroring back channel is generated for the relevant data point with the Value
monitoring function via which the locally changed value is mirrored back.
Remember that to use the mirror back function, you need to interconnect the local values in
the controller with the relevant PLC tag of the data point.
2: Block of data
With the ARRAY data type, blocks of data from contiguous memory areas up to a size of
4 .. 48 bytes can be transferred.
Compatible components of ARRAY are DINT, UDINT, DWORD or REAL. The components
within an array must be of the same type.
If the array is modified later, the data point must be recreated.
4.7.11
Data point configuration
Note
Status identifiers
The CP 1243-8 IRC does not supply any status identifiers.
Below you will find notes on the individual parameters of the data points of the CP 1243-8
IRC.
If the tooltips of STEP 7 refer to sections in the information system that are valid for several
CP types, the particular behavior of the CP 1243-8 is described at this point.
Parameters in the "General“ tab
Data point index
The data point indexes must be unique in a CP.
Data point indexes assigned more than once in a CP are indicated as errors in the
consistency check and prevent the STEP 7 project being compiled.
Содержание CP 1243-8 IRC
Страница 10: ...Table of contents CP 1243 8 IRC 10 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 104: ...Diagnostics and upkeep 6 3 Module replacement CP 1243 8 IRC 104 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 112: ...Approvals CP 1243 8 IRC 112 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 114: ...Dimension drawings CP 1243 8 IRC 114 Operating Instructions 06 2015 C79000 G8976 C385 01 Figure B 2 From above ...
Страница 134: ...Accessories C 4 Connecting cables CP 1243 8 IRC 134 Operating Instructions 06 2015 C79000 G8976 C385 01 ...