Configuration and operation
4.7 Configuration in STEP 7 Basic
CP 1243-8 IRC
Operating Instructions, 06/2015, C79000-G8976-C385-01
87
Status Meaning
84xx
Other error message from the e-mail server
Apart from the leading "8", the status corresponds to the three-digit error number of the
SMTP protocol.
8500
Syntax error: Command unknown.
This also includes the error of having a command chain that is too long. The cause may be
that the e-mail server does not support the LOGIN authentication method.
Try sending e-mails without authentication (no user name).
8501
Syntax error. Check the following configuration data:
Message configuration > Message parameters:
•
Recipient address ("To" or "Cc").
8502
Syntax error. Check the following configuration data:
Message configuration > Message parameters:
•
Email address (sender)
8535
SMTP authentication incomplete. Check the "User name" and "Password" parameters in
the CP configuration.
8550
SMTP server cannot be reached. You have no access rights. Check the following configu-
ration data:
•
CP configuration > E-mail configuration:
–
User name
–
Password
–
Email address (sender)
•
Message configuration > Message parameters:
–
Recipient address ("To" or "Cc").
8554
Transfer failed
85xx
Other error message from the e-mail server
Apart from the leading "8", the status corresponds to the three-digit error number of the
SMTP protocol.
Include value
If you enable the option "Include value", the CP sends a value for the placeholder $$ from
the memory area of the CPU in the message. To do this, you configure a PLC tag whose
value is integrated in the message.
The value is entered in the message text instead of the placeholder $$.
Содержание CP 1243-8 IRC
Страница 10: ...Table of contents CP 1243 8 IRC 10 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 104: ...Diagnostics and upkeep 6 3 Module replacement CP 1243 8 IRC 104 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 112: ...Approvals CP 1243 8 IRC 112 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 114: ...Dimension drawings CP 1243 8 IRC 114 Operating Instructions 06 2015 C79000 G8976 C385 01 Figure B 2 From above ...
Страница 134: ...Accessories C 4 Connecting cables CP 1243 8 IRC 134 Operating Instructions 06 2015 C79000 G8976 C385 01 ...