Installation, connecting up, commissioning
3.1 Important notes on using the device
CP 1243-8 IRC
38
Operating Instructions, 06/2015, C79000-G8976-C385-01
WARNING
The equipment is designed for operation with Safety Extra-Low Voltage (SELV) by a
Limited Power Source (LPS).
This means that only SELV / LPS complying with IEC 60950-1 / EN 60950-1 / VDE 0805-1
must be connected to the power supply terminals. The power supply unit for the equipment
power supply must comply with NEC Class 2, as described by the National Electrical Code
(r) (ANSI / NFPA 70).
If the equipment is connected to a redundant power supply (two separate power supplies),
both must meet these requirements.
WARNING
EXPLOSION HAZARD
DO NOT CONNECT OR DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR
COMBUSTIBLE ATMOSPHERE IS PRESENT.
WARNING
EXPLOSION HAZARD
SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION
2 OR ZONE 2.
WARNING
When used in hazardous environments corresponding to Class I, Division 2 or Class I,
Zone 2, the device must be installed in a cabinet or a suitable enclosure.
3.1.2
Notices about use in hazardous areas according to ATEX
WARNING
Requirements for the cabinet/enclosure
To comply with EU Directive 94/9 (ATEX95), the enclosure or cabinet must meet the
requirements of at least IP54 in compliance with EN 60529.
Содержание CP 1243-8 IRC
Страница 10: ...Table of contents CP 1243 8 IRC 10 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 104: ...Diagnostics and upkeep 6 3 Module replacement CP 1243 8 IRC 104 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 112: ...Approvals CP 1243 8 IRC 112 Operating Instructions 06 2015 C79000 G8976 C385 01 ...
Страница 114: ...Dimension drawings CP 1243 8 IRC 114 Operating Instructions 06 2015 C79000 G8976 C385 01 Figure B 2 From above ...
Страница 134: ...Accessories C 4 Connecting cables CP 1243 8 IRC 134 Operating Instructions 06 2015 C79000 G8976 C385 01 ...