Parameter assignment
7.29 Measurement
SITRANS Probe LR with mA/HART
70
Operating Instructions, 05/2019, A5E32337711-AC
7.29.2
P920 Reading measurement
P920 corresponds to the final reading after all programming is applied. It is a copy of one of
P921 to P924, depending on the setting for Operation (P001).
Operation P001
Source parameter for P920
0
Off
----
1
Level
P921 if P050 = 0, otherwise P924
2
Space
P922
3
Distance
P923
P920 Values (read only)
Range
–99999 to 99999 (dimensional units, if volume has not
been selected)
7.29.3
P921 Material measurement
Displays the distance between Empty/process empty level (P006) and the monitored
surface, in Units (P005) or percent of Span (P007).
Values (view only)
Range
–99999 to 99999
7.29.4
P922 Space measurement
Displays the distance between the monitored surface and Span / process full level (P007).
Values (view only)
Range
–99999 to 99999
7.29.5
P923 Distance measurement
Displays the distance between the monitored surface and the reference point. For the
reference point for the standard model, see SITRANS Probe LR dimensions (Page 84).
Values (view only)
Range
–99999 to 99999
7.29.6
P924 Volume measurement
Note
The display for P924 reads - - - -, when volume calculation is not enabled at P050 (P050 =
0).
The calculated vessel capacity in Maximum Volume (P051) or percent of Maximum Volume
(volume calculation must be enabled at P050).
Values (view only)
Range
–99999 to 99999
Related parameters
P051 Maximum volume
P050 Vessel shape