Parameter assignment
7.11 P051 Maximum volume
SITRANS Probe LR with mA/HART
48
Operating Instructions, 05/2019, A5E32337711-AC
P050
Value
Vessel shape
Description
Also required
8
sphere
P051
9
universal linear level/volume break-
points
P051, P054, P055
7.11
P051 Maximum volume
For readings in volumetric units instead of percentage values, enter the vessel volume
between Empty (P006) and Span (P007). Any volumetric units can be chosen, because the
volume calculation is based on the maximum volume, and scaled according to the Vessel
Shape (P050) value. If no value is entered, the default is 100, and the reading will be a
percentage value.
Values
Range
0.0000 to 99999
Default
100.0
Related parameters
P006 Empty
P007 Span
Enter the vessel volume between Empty (P006) and Span (P007).
1.
Key in the value. (For example, if maximum volume = 3650 m
3
, key in 3650.)
2.
Press ENTER
.
If the value is too large for the LCD display, enter larger units.
Example: If maximum volume = 267,500 gallons, key in 267.5 (thousands of gallons).
7.12
P052 Vessel dimension A
Dimension A as used for P050 Vessel Shapes 2, 3, 4, 5, or 7, in P050 Vessel shape
(Page 46).
Values
Range
0.0000 to 99999 in units (P005)
Default
0.0
Related parameters
P050 Vessel Shape
Enter one of the following, using the units selected in P005:
●
Height of the vessel bottom if P050 = 2, 3, 4, or 5
●
Length of one end-section of the vessel if P050 = 7