Commissioning
6.2 Local commissioning
SITRANS Probe LR with mA/HART
28
Operating Instructions, 05/2019, A5E32337711-AC
6.2.5
PROGRAM mode
Programming
Note
Do not use the handheld programmer at the same time as SIMATIC PDM, or erratic
operation may result.
●
Set parameters to suit your specific application.
●
Activate PROGRAM mode at any time, to change parameter values and set operating
conditions.
●
For local programming, use the Siemens handheld programmer.
●
For programming from a distance, use either a PC running SIMATIC PDM, or a HART
handheld communicator.
Display
①
Auxiliary Reading (displays parameter names for the Quick Start parameters, if a language is
selected. It displays the index value for indexed parameters, such as P054.)
②
Primary Reading (displays parameter value)
③
Secondary Reading (displays parameter number)
④
Programming indicator
6.2.6
Handheld programmer functions
The handheld programmer used with this device contains lithium batteries that are non-
replaceable.