Parameter assignment
7.15 P055 Volume breakpoints
SITRANS Probe LR with mA/HART
50
Operating Instructions, 05/2019, A5E32337711-AC
7.
Key in the level value for breakpoint 2, and press ENTER
. (Use units defined in
P005.)
8.
Repeat steps 6 and 7 until level values have been entered for all the required
breakpoints.
Breakpoint number
Level breakpoint (P054)
Volume breakpoint (P055)
1
0
0
2
4
500
3
8
3000
4
20
8000
7.15
P055 Volume breakpoints
Each segment defined by the level breakpoints (P054) requires a corresponding volume for
SITRANS Probe LR to make the level-to-volume calculations.
Primary Index
P055
Secondary Index
Breakpoint number
Values
Range
0.0000 to 99999 in units
Default
0.0000
Related parameters
P054 Volume Breakpoints
Typical volume calculations:
Cone
Cylinder