Parameter assignment
7.23 P752 HART address
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC
63
7.23
P752 HART address
Note
Accessible via the handheld programmer only by keying in P752.
Sets the device address or poll ID on a HART network. Any address other than 0 will cause
the output current to be a fixed value, and the current will not indicate the reading.
Values
Range
0 to 15 Enter 0 for single transmitter installation; enter digit
other than 0 for multi-drop applications. (Default: 0)
7.24
Communications (P799)
7.24.1
P799 Communications control
Enables the read/write access to parameters via remote communications.
Values
0
Read only
1
*
Read/write
2
Restricted access - read only except for P799 which is read/write
Note
•
P799 controls the access if you are using a HART master.
•
P000 controls the lock access if you are using the Siemens handheld programmer.
7.25
Echo processing (P800 to P807)
Note
Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly
described.
The following parameters are for authorized Siemens Service personnel or technicians
familiar with Siemens echo processing techniques. View the echo profile first, using
SIMATIC PDM, before attempting to modify these parameters.