Parameter assignment
7.17 Failsafe (P070 to P073)
SITRANS Probe LR with mA/HART
52
Operating Instructions, 05/2019, A5E32337711-AC
7.17
Failsafe (P070 to P073)
Note
Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly
described.
7.17.1
P070 Failsafe timer
Note
The last valid reading is maintained until the Failsafe timer expires. After the timer expires,
the reading is set based on P071.
Sets the time to elapse in minutes since the last valid reading, before Failsafe State
activates.
Values
Range
0.00 to 720 min.
Default
100.0 (based on P003)
7.17.2
P071 Failsafe material level
The material level to be reported when the Failsafe Timer expires. For more detail, see
Values
1
Use Maximum mA Limit (P213) as material level
2
Use Minimum mA Limit (P212) as material level
3
*
Level remains at last reading
4
User-selected value (defined in P073)
1.
Enter the value corresponding to the level you want reported when the Failsafe Timer
expires.
2.
Press ENTER
.
7.17.3
P073 Failsafe level
Note
P071 must be set to User-selected value (4) to use this value.
Defines a user-defined level to report when the Failsafe timer expires.
Values
Range
3.6 mA to 22.6 mA
Default
22.6 mA