Commissioning
6.2 Local commissioning
SITRANS Probe LR with mA/HART
36
Operating Instructions, 05/2019, A5E32337711-AC
6.2.11.3
P003: Measurement response
Set response time to filling/emptying rate (P003: Measurement Response)
Set P003 to a measurement response speed just faster than the maximum filling or emptying
rate (whichever is greater).
Parameter
Values Description
Parameters affected by P003
1
*
Slow
0.1m/minute
P070, P700, P701, P709, P711
2
Medium
1m/minute
3
Fast
10m/minute
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy: faster settings allow for more level fluctuation.
(For more detail on measurement response, see Transceiver (Page 86))
P004 Antenna type (view only)
Value
240
rod antenna
6.2.11.4
P005: Units
Select the measurement units required (P005: Units)
Parameter
Value
Description
P005
1
*
meters
2
centimeters
3
millimeters
4
feet
5
inches
6.2.11.5
P006: Empty
Set process empty level (P006: Empty)
Value
Range
0.0000 to 20.00
Default
20.00 m (maximum range)
Enter the distance from the antenna reference point
1)
to process empty level (Empty), using
units set in P005. Empty can be set to any distance: not necessarily the bottom of the vessel.
For reference point, see SITRANS Probe LR dimensions (Page 84).