Parameter assignment
7.4 P004 Antenna type
SITRANS Probe LR with mA/HART
44
Operating Instructions, 05/2019, A5E32337711-AC
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy: faster settings allow for more level fluctuation.
●
Echo Verification (P711): discriminates between agitator blades in motion (spurious
noise) and the target surface (true echo).
●
Failsafe timer (P070): establishes the period from the time a loss of echo (LOE) starts
until the Failsafe default (P071) is triggered. P070 takes precedence over P003.
7.4
P004 Antenna type
Specifies the antenna type attached.
Values
240 * rod antenna
7.5
P005 Units
Specifies measurement units used for dimensional values.
Values
1
*
meters
2
centimeters
3
millimeters
4
feet
5
inches
7.6
P006 Empty (process empty level)
Sets the distance from the reference point to the process empty level, in units selected at
P005.
For the reference point, see SITRANS Probe LR dimensions (Page 84).
Values
Range
0.0000 to 20.00 (m)
Default
20.00 m (max. range)
Enter the distance from the reference point to Empty (process empty level), using units set in
P005. Empty can be set to any distance: not necessarily the bottom of the vessel.