Explanation of the parameters
Parameters
5__
Monitoring functions
50_
Speed monitoring
The drive only attains the speed required by the setpoint if it has sufficient torque. If the inverter reaches
P303 Current
limit, this is because it did not attain the required speed. Speed monitoring is triggered if the inverter exceeds the current
limit for longer than set in
P501 Delay time.
500
•
Speed monitoring
0 / OFF
3 / MOT Function of speed monitoring in motor and regenerative operation
of the motor
501
•
Delay time
Setting range 0 ... 1 ... 10 [s]
The set current limit may be reached briefly during acceleration and decel-
eration procedures or when load peaks occur. You can set the delay time to
prevent an over-sensitive response from the speed monitoring function. The
current limit must be attained uninterruptedly for the duration of the delay
time before the monitoring function responds.
6__
Terminal assignment
60_
Binary inputs
Effect of
0 signal
1 signal
NO FUNCTION:
-
-
ENABLE/RAP.STOP:
Rapid stop with
P136 Stop ramp
Enable
CW/STOP: Stop
with
P131 Ramp DOWN CW
enable
CCW/STOP: Stop
with
P131 Ramp DOWN CCW
enable
FIX SETPT SW.OV:
Fixed setpoints n11/n12/n13
Fixed setpoints n21/n22/n23
MOTOR POT UP:
-
Increase setpoint
MOTOR POT DOWN:
-
Reduce setpoint
/EXT. FAULT:
External fault
-
FAULT RESET:
Reset on positive edge 0 to 1
SETPOINT HOLD:
Do not take over
Take over setpoint
TF RESPONSE (DI05 only):
Overtemperature in motor
No signal
/CONTROL.INHIBIT: Inhibit
Enable
IPOS INPUT:
Depends on LOGODrive program
Fixed setpoints
n11/n21 = 0 and n12/n22 = 0:
External setpoints only
n11/n21 = 1 and n12/n22 = 0:
n11/n21
n11/n21 = 0 and n12/n22 = 1:
n12/n22
n11/n21 = 1 and n12/n22 = 1:
n13/n23
60-
•
Binary inputs
Binary input DI01 has a fixed
setting of CW/STOP.
DI02
DI03
DI04
DI05
0
CCW/STOP
FIX SETP SW.OVn11/n21
n12/n22
1
CCW/STOP
ENABLE
n11/n21
n12/n22
2
CCW/STOP
ENABLE
MOT..POT UP
MOT. POT DOWN
3
ENABLE
FIX SETP SW.OVn11/n21
n12/n22
4
CCW/STOP
SETPT HOLD
n11/n21
n12/n22
5
CCW/STOP
ENABLE
/EXT. FAULT
FAULT RESET
6
CCW/STOP
ENABLE
FAULT RESET
TF RESPONSE
7
CCW/STOP
/EXT. FAULT
n11/n21
n12/n22
8
CCW/STOP
ENABLE
n11/n21
/CTRL.INHIBIT
-
(Deviating combination set with MOVITOOLS)
601
Binary input DI02
Factory setting: CCW/STOP
602
Binary input DI03
Factory setting: ENABLE
603
Binary input DI04
Factory setting: n11/n21
604
Binary input DI05
Factory setting: n12/n22
No.
OP Name
Description
P6..
P60.
P600