![SEW-Eurodrive MOVITRAC 07 Скачать руководство пользователя страница 128](http://html1.mh-extra.com/html/sew-eurodrive/movitrac-07/movitrac-07_system-manual_1250133128.webp)
8
128
System Manual – MOVITRAC® 07
Installation instructions
Installation
8
Installation
8.1
Installation instructions
Tightening
torques
•
Only use genuine connection elements. Note the permitted tightening torques
of MOVITRAC
®
07 power terminals.
– Size 0S/M/L
→
0.5 Nm (4.4 lb.in)
– Size 1
→
0.6 Nm (5.3 lb.in)
– Size 2S/2
→
1.5 Nm (13.3 lb.in)
– Size 3
→
3.5 Nm (31 lb.in)
– Size 4
→
14 Nm (124 lb.in)
Recommended
tools
•
Use a screwdriver with a 2.5 mm wide blade for connecting the electronics terminal
strip X10.
Conductor end
sleeves
•
The terminals are provided for installation without conductor end sleeves.
Minimum clear-
ance and mount-
ing position
•
Leave 100 mm (4 in) clearance at the top and bottom for optimum cooling. No lat-
eral clearance required; the units can be lined up side-by-side. Make sure that the
circulation of air is not disrupted by cables or other installation materials. Prevent the
heated exhaust air from other units from blowing onto this unit. With sizes 4 and 5,
do not install any components which are sensitive to high temperatures within 300
mm (11.81 in) of the top of the unit. Only install the units vertically. You must not
install them horizontally, tilted or upside down.
It is essential to comply with the safety notes during installation!
02475AXX
Figure 71: Note the tightening torques
Nm (lb.in)!
Содержание MOVITRAC 07
Страница 1: ...MOVITRAC 07 Edition 02 2003 System Manual 1056 2915 EN...
Страница 2: ...SEW EURODRIVE...
Страница 6: ...6 System Manual MOVITRAC 07 Contents...
Страница 165: ...MOVITRAC 07 Edition 12 2003 Addendum to the System Manual 11254114 EN...