Explanation of the parameters
Parameters
15_
Motor potentiometer function (see
P100 Setpoint source)
150
•
Ramp t3 (motor potentiome-
ter)
Setting range 0.2 ... 20 ... 50 [s]
The ramp takes effect when the
Motor pot. up and Motor pot. down terminal
functions are used.
152
•
Save last setpoint
off / OFF
The inverter starts with n
min
:
•
After supply system off/on
•
After the enable has been revoked
You must set
P152 Save last setpoint = OFF if you are using the motor
potentiometer for continuous speed control. Otherwise, fault message
F25 EEPROM will appear after about 100,000 storage operations.
Store only after setpoint change.
on / ON
The inverter starts with the last motor potentiometer setpoint to have
been set:
•
After supply system off/on
•
After the enable has been revoked
16_
Fixed setpoints (set 1)
The fixed setpoints can be activated via binary inputs DI02 ... DI05 by setting arguments n11/n21 / n12/n22 and FIX
SETPT SW.OV (parameter 60_). Fixed setpoints n13/n23 are activated when two binary inputs are occupied with the
n11/n21 and n12/n22 functions and both have 1 signals.
160
•
Internal setpoint n11
Setting range 0 ... 150 ... 5000 [rpm]
161
•
Internal setpoint n12
Setting range 0 ... 750 ... 5000 [rpm]
162
•
Internal setpoint n13
Setting range 0 ... 1500 ... 5000 [rpm]
163
•
Internal setpoint n11 PI-con-
troller
Setting range 0 ... 3 ... 100 [%] (see Sec. Project Planning / PI-controller)
164
•
Internal setpoint n12 PI-con-
troller
Setting range 0 ... 15 ... 100 [%] (see Sec. Project Planning / PI-controller)
165
•
Internal setpoint n13 PI-con-
troller
Setting range 0 ... 30 ... 100 [%] (see Sec. Project Planning / PI-controller)
17_
Fixed setpoints (set 2)
170
•
Internal setpoint n21
Setting range 0 ... 150 ... 5000 [rpm]
171
•
Internal setpoint n22
Setting range 0 ... 750 ... 5000 [rpm]
172
•
Internal setpoint n23
Setting range 0 ... 1500 ... 5000 [rpm]
173
•
Internal setpoint n21 PI-con-
troller
0 ... 3 ... 100 [%] (see Sec. Project Planning / PI-controller)
174
•
Internal setpoint n22 PI-con-
troller
0 ... 15 ... 100 [%] (see Sec. Project Planning / PI-controller)
175
•
Internal setpoint n23 PI-con-
troller
0 ... 30 ... 100 [%] (see Sec. Project Planning / PI-controller)
No.
OP Name
Description
P6..
P60.
P600