Explanation of the parameters
Parameters
112
•
AI1 operation mode
0 / 3000 rpm (0 – 10 V)
Voltage input with reference 3000 rpm (0 ... 10 V = 0 ... 3000 rpm). You
can adapt the characteristic curve with
AI1 scaling.
Switch S11 = V
1 / N-MAX (0 – 10 V)
Voltage input with reference n
max
(0 ... 10 V = 0 ... n
max
). You can adapt
the characteristic curve with
AI1 scaling.
Switch S11 = V.
5 / N-MAX (0 – 20 mA)
Current input 0 ... 20 mA = 0 ... n
max
. P110 AI1 scaling is ineffective.
Switch S11 = mA.
6 / N-MAX (4 – 20 mA)
Current input 4 ... 20 mA = 0 ... n
max
.
P110 AI1 scaling is ineffective.
Switch S11 = mA.
12_
Analog input 2 (setpoint potentiometer of the integrated operating panel)
121
•
Addition Setpoint Potentiom.
of the operating panel
0 / OFF
The unit does not take into account the value of the setpoint potentiome-
ter of the integrated operating panel.
1 / ON
The value of the setpoint potentiometer of the integrated operating panel
is added to any set setpoint source UNIPOL./FIX.SETPT, RS485, SBus
or analog input AI1 or fixed setpoints.
2 / ON EXCEPT FSP
The value of the setpoint potentiometer of the integrated operating panel
is added to any set setpoint source UNIPOL./FIX.SETPT, RS485, SBus
or analog input AI1. The addition does not act on fixed setpoints.
122
•
Local Potentiometer Mode
(only in manual mode)
0 / UNIPOL. CW
Setting the setpoint with the setpoint potentiometer of the integrated
operating panel in "manual speed control module" mode.
Speed setting range: 0 ... + n
max
.
1 / UNIPOL. CCW
Setting the setpoint with the setpoint potentiometer of the integrated
operating panel in "manual speed control module" mode.
Speed setting range: 0 ... - n
max
.
2 / BIPOL.CW+CCW
Setting the setpoint with the setpoint potentiometer of the integrated
operating panel in "manual speed control module" mode.
Speed setting range: - n
max
... + n
max
.
13_
Speed ramps
The ramp times refer to a setpoint change of
∆
n = 3000 rpm. Ramps t11 UP and t11 DOWN are effective when the set-
point is changed. The stop ramp t13 is in effect when the enable is withdrawn with the STOP/RESET key or via the ter-
minals.
130
•
Ramp t11 UP
Setting range 0.1 ... 2 ... 2000 [s]; acceleration ramp
131
•
Ramp t11 DOWN
Setting range 0.1 ... 2 ... 2000 [s]; deceleration ramp
136
•
Stop ramp t13
Setting range 0.1 ... 2 ... 20 [s]; stop ramp when switching to the NO
ENABLE operating status
138
Ramp limit
0 / NO
1 / YES
This parameter can be used for deactivating the software current limitation
and therefore also the pull-out protection. The inverter switches off with fault
message F-01 (overcurrent) if the apparent current is above the limit value
160 % for t > 100 ms. SEW recommends not switching off the ramp limit.
No.
OP Name
Description
P6..
P60.
P600