![SEW-Eurodrive MOVITRAC 07 Скачать руководство пользователя страница 109](http://html1.mh-extra.com/html/sew-eurodrive/movitrac-07/movitrac-07_system-manual_1250133109.webp)
System Manual – MOVITRAC® 07
109
5
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Connecting the optional power components
Project Planning
5.15
Connecting the optional power components
Series ND... line
chokes
Series NF...-... line
filters
Series HD... out-
put chokes
Series HF... out-
put filters
•
Restrict the length of the cable between the inverter and the output filter to the abso-
lute minimum needed. Maximum 1 m / 3.3 ft with an unshielded cable and 10 m / 33
ft for a shielded cable.
05259AXX
Figure 56: Connecting ND... line chokes
05260AXX
Figure 57: Connecting NF...-... line filters
Output choke type
HD001
HD002
HD003
For cable cross sec-
tions
1.5...16 mm
2
(AWG16...6)
≤
1.5 mm
2
(
≤
AWG16)
≥
16 mm
2
(
≥
AWG6)
•
Install output filters next to the corresponding inverter. Leave a ventilation space of
at least 100 mm (4 in) below and above the output filter. No clearance is required to
either side.
•
You are only allowed to connect unshielded motor leads if using an output filter. A
shielded motor lead leads to impermissibly high heating of the output filter.
Содержание MOVITRAC 07
Страница 1: ...MOVITRAC 07 Edition 02 2003 System Manual 1056 2915 EN...
Страница 2: ...SEW EURODRIVE...
Страница 6: ...6 System Manual MOVITRAC 07 Contents...
Страница 165: ...MOVITRAC 07 Edition 12 2003 Addendum to the System Manual 11254114 EN...