![SEW-Eurodrive MOVITRAC 07 Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/sew-eurodrive/movitrac-07/movitrac-07_system-manual_1250133066.webp)
4
66
System Manual – MOVITRAC® 07
Explanation of the parameters
Parameters
0__
Display values
This group of parameters contains information about
•
Process values
•
Statuses
•
Fault memory the unit
00_
Process values
000
Speed (signed) [rpm]
Resolution 1 rpm.
The displayed speed is the calculated actual speed.
002
Frequency (signed) [Hz]
Output frequency of the inverter.
004
Output current (value)
[% I
N
]
Apparent current in the range 0 ... 200 % of the rated unit current.
005
Active current (signed) [% I
N
]
Active current in the range 0 ... 200 % of the rated unit current. The dis-
played value is positive when the torque is in the positive sense of rotation;
it is negative when the torque is in the negative sense of rotation.
008
DC link voltage [V]
DC link voltage.
009
Output current [A]
Apparent current at the inverter output, displayed in A
AC
.
01_
Status displays
010
Inverter status
Status of the unit output stage
•
INHIBITED
•
ENABLED
011
Operational status
The following operational states are possible:
•
CONTROL.INHIBIT
•
NO ENABLE
•
ENABLE
•
FACTORY SETTING
•
FAULT
•
CURRENT AT STANDSTILL
012
Fault status
Fault number and fault in plain text.
014
Heat sink temperature [°C]
Heat sink temperature of the inverter.
02_
Analog setpoints
020
Analog input AI1 [V]
Voltage 0 ... +10 V at analog input AI1. When S11 = ON and
P112 AI1 oper-
ation mode:
•
= NMAX, 0 ... 20 mA: Display 0 ... 5 V = 0 ... 20 mA
•
= NMAX, 4 ... 20 mA: Display 1 ... 5 V = 4 ... 20 mA
03_
Binary inputs
031
Binary input DI01
Status of binary input DI01 (CW/STOP = fixed assignment)
032
Binary input DI02
Status of binary input DI02 (CCW/STOP = fixed assignment)
033
Binary input DI03
Status of binary input DI03 (ENABLE/RAP.STOP = factory setting)
034
Binary input DI04
Status of binary input DI04 (n11/n21 = factory setting)
035
Binary input DI05
Status of binary input DI05 (n12/n22 = factory setting)
036
Binary inputs DI01..DI05
Collective display of the binary inputs.
05_
Binary outputs
051
Binary output DO01
Status of binary output DO01 (/FAULT = factory setting)
052
Binary output DO02
Status of binary output DO02 (BRAKE RELEASED = factory setting)
053
Binary outputs DO01, DO02
Collective display of the binary outputs.
No.
OP Name
Description
P6..
P60.
P600