List of errors (F-00 ... F-97)
Operation and Service
11
Overtempera-
ture
Rapid stop
with inhibit
Thermal overload of inverter
•
Reduce load and/or ensure ade-
quate cooling
•
If the braking resistor is integrated
in the heat sink: Mount the braking
resistor externally
17-
24
System fault
Immediate
switch-off
Inverter electronics disrupted, possibly
due to effect of EMC
Check ground connections and
shields; improve them if necessary.
Contact SEW Service for advice if this
reoccurs.
25
EEPROM
Rapid stop
with inhibit
Fault when accessing EEPROM
Call up default setting, perform reset
and set parameters again. Contact
SEW Service for advice if this reoc-
curs.
26
External termi-
nal
Programma-
ble
Read in external fault signal via pro-
grammable input
Eliminate specific cause of fault; repro-
gram terminal if appropriate.
31
TF sensor
Rapid stop
with inhibit
•
Motor too hot, TF sensor has
tripped
•
TF sensor of motor not connected
or not connected properly
•
Connection of MOVITRAC
®
07 and
TF interrupted on motor
•
Let motor cool down and reset fault
•
Check connections/links between
MOVITRAC
®
07 and TF
32
Index overrun
Emergency
stop
Basic programming rules violated
causing internal stack overflow
Check and correct user program
34
Ramp timeout
Immediate
switch-off
The inverter signals F34 if you revoke
the enable and the drive exceeds the
rapid stop ramp time t13 by a certain
time.
Extend the rapid stop ramp time
37
Watchdog timer Immediate
switch-off
Fault in system software sequence
Check ground connections and
shields; improve them if necessary.
Contact SEW Service for advice if this
reoccurs.
38
System soft-
ware
Immediate
switch-off
System fault
Check ground connections and
shields; improve them if necessary.
Contact SEW Service for advice if this
reoccurs.
43
RS-485 timeout
Rapid stop
without
inhibit
1
Communication between inverter and
PC interrupted
Check connection between inverter
and PC.
44
Unit utilization
Immediate
switch-off
Unit utilization (Ixt value) excessive
•
Reduce power output
•
Extend ramps
•
If these points are not possible:
Use a larger inverter
No.
Name
Response
Possible cause
Action