Explanation of the parameters
Parameters
Control signal source 3-WIRE-CONTROL
X10:2 =
CW/STOP
X10:3 =
CCW/STOP
X10:4 =
Enable/Rapid
stop
X10:13/14 = Set-
point input AI
f
A
= Output fre-
quency
f
0
= Start/stop fre-
quency
CW = Turning to
the right
CCW = Turning to
the left
t11 [1] = t11 UP
t11 [2] = t11
DOWN
t13 = Rapid stop
ramp
102
•
Frequency scaling (in prepa-
ration)
Setting range 0.1 ... 10 ... 65.00 [kHz]
11_
Analog input 1 (+10 V)
110
•
AI1 scaling
Setting range: 0.1 ... 1 ... +10.
This defines the slope of the setpoint characteristic curve. If you set the
scaling to the value "1", then the input voltage V
I
= 10 V at the analog input
corresponds to the operating mode of the analog input (P112). This is the
speed 3000 rpm or the set maximum speed (P302).
Slope of the setpoint characteristic curve
You can only use the 1st quadrant with a unipolar setpoint source. Negative
setpoint entries then create the setpoint zero. P110 AI1 scaling has no
effect if you set the current input operating mode. You set the current
input operating mode by setting P112 AI1 operation mode to NMAX, 0-
20 mA or NMAX, 4-20 mA.
No.
OP Name
Description
n
10
2
1
0.5
0.1
U
E
3000 rpm
/ n
max
10 V
P6..
P60.
P600