Doc. MI004620-I
S6001 Pump controller
Rev. 0
www.seneca.it
108 /
122
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION CAN
BE REPRODUCED WITHOUT PREVIOUS AUTHORIZATION.
User Manual
ES
Request the status of a 5-pump system
TX: STATUS
RX: SP=5.0 bar
PV=5.1 bar
P1:MAN RUN
P2:MAN STOP
P3:MAN ALR
P4:AUTO RUN
P5:AUTO STOP
WARNING:2
ALARMS:3
Tab. 80 SMS 4 command
COM
Enabling or disabling the sending of SMS on alarm to the user who sends the command. The
command does not exclude the calculation of alarms by the system
TX
SET ALARM <ON/OFF>
RX
SET ALARM <ON/OFF> OK
ES
TX: SET ALARM ON
RX: SET ALARM ON OK
Tab. 81 SMS 5 command
COM
System alarm resetting. The command resets the alarms as if a user were to press the RE
-
SET key on the “Alarms” page
(Fig. 52 on page 65)
of the system. The response to
the reset command is the same as the STATUS message.
TX
RESET ALARM
RX
SP=<Set Point value> <Set Point unit of measurement>
PV=<process variable value> <process variable unit of measurement>
P1:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR>
P2<MAN/AUTO> <RUN/RUN_INV/STOP/ALR>
P3:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
P4:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
P5:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
P6:<MAN/AUTO> <RUN/RUN_INV/STOP/ALR> (if present)
WARNING:<number of non-blocking alarms>
ALARMS:<numbers of blocking alarms>