S6001 Pump controller
Rev. 0
www.seneca.it
106 /
122
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION CAN
BE REPRODUCED WITHOUT PREVIOUS AUTHORIZATION.
User Manual
The system accepts commands
only
from the 3 numbers associated to the system in the
“Telecontrol” screen in
“1.1.8.5 “Telecontrol” screen” on page 91
.
P1, P2, etc. stand for pump 1, pump 2, etc. respectively.
The following acronyms are used in the following table:
- COM = command the system must execute;
- TX = SMS text to send to the system;
- RX = system answering SMS text;
- ES = example.
COM
Change the system operating mode setting it to AUTOMATIC or MANUAL.
TX
SET MODE <AUTO/MAN>
RX
SET MODE <AUTO/MAN> OK
ES
Set the system to automatic mode.
TX: SET MODE AUTO
RX: SET MODE AUTO OK
Tab. 77 SMS 1 command
COM
Changing the operating mode of the pump to AUTOMATIC/MANUAL and forcing it to start or
stop if it is set to MANUAL. If the command is sent to set a pump to automatic mode, the next
parameter <ON/OFF> is not necessary and, if present, is ignored. The command is execut
-
ed only if the pump you want to control is present in the system, otherwise it gives an error
(ERR). If the pump is in the fault state, any command given causes an alarm (ALR).
TX
SET <P1/P2/P3/P4/P5/P6> <AUTO/MAN> <ON/OFF>
RX
SET <P1/P2/P3/P4/P5/P6> <AUTO/MAN> <ON/OFF> <OK/ERR/ALR>
ES
P2 is in the system and in manual mode. Force the pump to switch off.
TX: SET P2 MAN OFF
RX: SET P2 MAN OFF OK
P1 is in the system and in automatic mode but is faulty. If the pump is forced to switch off, the
alarm is triggered.
TX: SET P1 MAN OFF
RX: SET P1 MAN OFF ALR
P6 is not in the system. If a command is sent, an error is returned.
TX: SET P6 AUTO ON
RX: SET P6 AUTO ERR
Tab. 78 SMS 2 command