Doc. MI004620-I
S6001 Pump controller
Rev. 0
www.seneca.it
101 /
122
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION CAN
BE REPRODUCED WITHOUT PREVIOUS AUTHORIZATION.
User Manual
Code
Alarm
Description
Cause
Solution
OT034
MAXIMUM FLOAT
An “ALARM LEVEL FLOAT”
signal has been configured
among the configurable digital
inputs, the contact connected
to this input is closed and the
pumps are running.
- Check the configuration of
the digital inputs in the SET
-
TINGS > IO DIGITAL TYPE
section of the HMI panel is
correct. Check the wiring of the
auxiliary contacts of the
“ALARM LEVEL FLOAT” signal
is correct. Check the installation
of the float in the tank is correct.
OT036
HIGH ADJUSTMENT PROBE
The adjustment probe con
-
nected to analogue input AI4
measures a level lower than
the value set for parameter H
in the SETPOINT> ANALOGUE
THRESHOLDS section of the
HMI panel
- Check the correct configu
-
ration of the digital inputs in
the SETPOINT > ANALOGUE
THRESHOLDS section of the
HMI panel. Check the wiring of
the adjustment probe is correct.
OT039
EXTERNAL ALARM
An “EXTERNAL ALARM” signal
has been configured among the
configurable digital inputs and
the contact connected to this
input is closed.
- Check the configuration of
the digital inputs in the SET
-
TINGS> IO DIGITAL TYPE
section of the HMI panel is cor
-
rect. - Check the wiring of the
auxiliary contacts of the “EX
-
TERNAL ALARM” signal is
correct.
OT040
UPS ALARM IN BATTERY OP-
ERATION
A “UPS NETWORK OK” signal
has been configured among the
configurable digital inputs and
the contact connected to this
input is open.
- Check the configuration of
the digital inputs in the SET
-
TINGS > IO DIGITAL TYPE
section of the HMI panel is
correct. Check the wiring of the
auxiliary contacts of the “UPS
NETWORK OK” signal is cor
-
rect.