Doc. MI004620-I
S6001 Pump controller
Rev. 0
www.seneca.it
105 /
122
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION CAN
BE REPRODUCED WITHOUT PREVIOUS AUTHORIZATION.
User Manual
Code
Alarm
Description
Cause
Solution
OT066
EXPANSION MODULE 2 COM-
MUNICATION ALARM
At least 5 pumps have been
configured, which requires
the installation of an expan
-
sion module for the P5 pump,
Z-D-IO type, connected to the
RS485 that does not respond to
MODBUS queries
- Check the RS485 data con
-
nection cable for correct con
-
nection and polarity of the A/B
signals between the pump
controller and the Z-D-IO ex
-
pansion module. Verify that the
parameters of the RS485 serial
set in the dip switches of the
Z-D-IO expansion module cor
-
respond to those configured in
the pump controller.
OT067
EXPANSION MODULE 3 COM-
MUNICATION ALARM
At least 6 pumps have been
configured, which requires
the installation of an expan
-
sion module for the P6 pump,
Z-D-IO type, connected to the
RS485 that does not respond to
MODBUS queries
- Check the RS485 data con
-
nection cable for correct con
-
nection and polarity of the A/B
signals between the pump
controller and the Z-D-IO ex
-
pansion module. Verify that the
parameters of the RS485 serial
set in the dip switches of the
Z-D-IO expansion module cor
-
respond to those configured in
the pump controller.
Tab. 76 Non-blocking alarms
1.1
REMOTE CONNECTIONS
Remote connections can be through:
SMS;
VPN protocol.
1.1.1 Remote connection via SMS
If the remote connection is provided by SMS, carry out the following operations in the given order:
1.
connect the main antenna to the port
(P8 -
Fig. 2 on page 12)
;
21.
if necessary, connect the diversity antenna to the port
(P9 -
Fig. 2 on page 12)
;
22.
insert the SIM into the slot
(P7 -
Fig. 2 on page 12)
;
23.
configure the SIM parameters as instructed in the “Mobile network configuration” sub-screen in
“1.1.8.5
“Telecontrol” screen” on page 91
, if not already configured using the wizard.
The following tables show all the possible commands that can be managed via SMS.
Содержание S6001
Страница 1: ...ORIGINAL INSTRUCTIONS USER MANUAL S6001 Pump controller...
Страница 2: ......