![Schweitzer Engineering Laboratories SEL-321 Скачать руководство пользователя страница 73](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-321/sel-321_instruction-manual_1216711073.webp)
Date Code 20011026
Specifications
2-49
SEL-321/321-1 Instruction Manual
T
ECHNICAL
S
PECIFICATIONS
(5 A N
OMINAL
R
ELAY
)
General Element Ranges and Accuracy
Phase Mho
Distance
Secondary Reach Setting Range:
0.05 - 64
Ω
at the line angle
Ground
Mho Distance
Secondary Reach Setting Range:
│
k
01
│
and
│
k
0
│
setting range*:
Angle k
01
and k
0
setting range*:
0.05 - 64
Ω
at the line angle
0 - 4
±180° in 0.1° steps
*
Note:
Same setting applies to Quadrilateral Ground Distance.
Quadrilateral
Distance
Secondary Reactive Reach:
Secondary Resistive Reach:
Nonhomogeneous Factor (T, degrees):
0.05 - 64
Ω
0.05 - 50
Ω
±20° in 0.1° steps
Out-of-Step
Distance
Secondary Reactance Setting Range:
Secondary Resistance Setting Range:
±96
Ω
±70
Ω
Load
Encroachment
Detection
Secondary Impedance Setting Range:
Forward Load Angle Setting (in degrees):
Reverse Load Angle Setting (in degrees):
0.05 - 64
Ω
-90° to +90°
+90° to 270°
Distance Element
Accuracy
Secondary Steady-State Error:
±5% of set reach ±0.01
Ω
at line angle (LA) for V > 5 V and I > 2 A
±10% of set reach ±0.01
Ω
at LA for 1 V < V < 5 V and 1 A < I < 2 A
Transient Overreach Error:
±5% of set reach, plus steady-state error
Negative-Sequence
Directional
Element
Secondary Positive-Sequence Current Restraint Range:
Secondary Forward Directional Current Supervision:
Secondary Reverse Directional Current Supervision:
Secondary Forward Directional Impedance Setting:
Secondary Reverse Directional Impedance Setting:
0.02 - 0.5
0.25 - 5 A
0.25 - 5 A
±64
Ω
±64
Ω
Supervisory
Overcurrent
Phase
Secondary Pickup Setting Range:
•
Supervises ground distance
0.5 - 100 A, ±0.05 A, ±3% of setting
Phase-to-Phase
Secondary Pickup Setting Range:
•
Supervises phase distance
1.0 - 170 A, ±0.05 A, ±3% of setting
Positive-Sequence
Secondary Pickup Setting Range:
•
Supervises OOS logic
1.0 - 100 A, ±0.05 A, ±3% of setting
Residual
Secondary Pickup Setting Range:
Transient Overreach:
•
Supervises ground distance
0.5 - 100 A, ±0.05 A, ±3% of setting
±5% of pickup
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......