Date Code 20011026
Maintenance and Testing
7-59
SEL-321/321-1 Instruction Manual
if VALID is Y, it is no longer displayed. Execute the
SET 1
command to enter the
correct group settings for your application, and set VALID and LOGVAL to Y.
Step 10.
Execute the
SHO F
command and review displayed data. Confirm that the I/O
board settings match those displayed in Step 1. If any I/O board settings do not
match, you must enter the correct settings. Note that some default settings may have
changed.
For example, if the output board configuration settings (IOBRD1 and/or IOBRD2)
do not match the number of output contacts on your relay, you must change the
output board configuration setting. To change the output board configuration
setting, you must enter the Calibration access level by executing the
CAL
command.
The password for Calibration access level is
CLARKE
.
Execute the
SET F
command to change the board configuration settings. Change the
IOBRD1 and/or the IOBRD2 (if equipped with a second output board) settings to
match the output board configuration. Set IOBRD1 = 8 for an 8 contact output board
configuration, IOBRD1 = 12 for a 12 contact output board configuration, and
IOBRD1 = 16 for a 16 contact output board configuration. Enter the output board
configuration setting for IOBRD2 if the relay is equipped with a second output
board.
Note that IOBRD1 refers to the interface board terminating on relay terminals 201
through 240. IOBRD2 refers to the interface board terminating on relay terminals
301 through 340.
Execute the
SET L 1
command to enter the correct SEL
OGIC
control equations for
your application. Execute the
COPY
command or the
SET
and
SET L
commands
to enter settings for each of the remaining groups (six total).
Execute the
STATUS
,
METER
, and
TRIGGER
commands to ensure that all
functions are operational. Set and record your Access Level 1, Breaker Access
Level, and Access Level 2 passwords and the date and time.
Step 11.
With relay communications still established and at Access Level 2, execute the
SHOWSET C
command and review displayed data. If data is identical to
previously recorded data of Step 1, you may execute the
QUIT
command, and the
relay is ready for your commissioning procedure. If, however, any channel gains are
different, you must reenter the previously recorded values by executing the
SET C
command (similar to group settings procedure). Make sure VALID = Y (Note:
VALID will only be present in the settings if defaults have been reloaded). After
this procedure is completed and changes have been saved, execute the
QUIT
command. The relay is now ready for your commissioning procedure.
Step 12.
If a new serial number label is included with the upgrade, attach the serial number
label so the old label is covered.
Step 13.
If you have any questions, please do not hesitate to telephone us for assistance.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......