Date Code 20011026
Special Application Settings
F-1
SEL-321/321-1 Instruction Manual
APPENDIX F: SPECIAL APPLICATION SETTINGS
Some settings have special values to actuate line specific features. These are documented in this
appendix.
V
ALUE OF
“S”
FOR
E51N, E51Q
With typical settings of “Y” or “N”, the time overcurrent accumulation is blocked for a single-
pole open (SPO) condition. When E51N is set to “S”, SPO does not block the 51N elements.
When E51Q is set to “S”, SPO does not block the 51Q elements.
V
ALUE OF
“N1”
OR
“Y1”
FOR
ESPT S
ETTING
N1 activates special Scheme 1 Trip Logic if the SPTE contact enables single-pole tripping.
Y1 activates special Scheme 1 Trip Logic equations:
Figure F.1: Scheme 1 Trip Decision Logic for Phase A
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......