2-40
Specifications
Date Code 20011026
SEL-321/321-1 Instruction Manual
Active Groups and Group Variables
The relay only uses one group setting at a time. The other setting groups are stored in
nonvolatile memory.
The setting group used at any one time is called the Active Group. Contact inputs control the
Active Group selection. The setting group selected by the GROUP command is labeled Group
Variable. If the inputs select Group Variable, the GROUP command controls the setting group
selection.
Global Settings
Inputs
SS1 - SS3
Assign to any input. Assignment order is not important.
Timed Group Reset TGR
Minimum delay that inputs (or input) selecting a new
setting group must be asserted before group is switched.
M
ETERING
Units:
Primary, computed from secondary inputs times instrument transformer ratio
settings.
Accuracy:
±1.0% of nominal input at rated voltage and current.
S
YSTEM
F
REQUENCY
T
RACKING
The relay adjusts its sampling rate by monitoring the system frequency using a zero-crossing
detector on the A-phase voltage input. The relay can be ordered with a nominal frequency of
either 60 or 50 Hz.
The frequency tracking range is 55 to 65 Hz for 60 Hz relays and 45 to 55 Hz for 50 Hz relays.
When the relay is first powered on, it assumes the nominal frequency.
Accuracy:
±0.028 Hz at 60 Hz
±0.020 Hz at 50 Hz
F
AULT
L
OCATOR
Fault locations are computed from data stored in the event report.
Select the fault locating method in the relay settings: set LOCAT = Y when there are current
sources in front of the relay location, and set LOCAT = R for radial applications. Set LOCAT =
N to disable the fault location feature.
One of the elements in Table 2.26 must assert in the event report data for the relay to calculate a
fault location.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......