![Schweitzer Engineering Laboratories SEL-321 Скачать руководство пользователя страница 272](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-321/sel-321_instruction-manual_1216711272.webp)
7-2
Maintenance and Testing
Date Code 20011026
SEL-321/321-1 Instruction Manual
Figure 7.1: Relay Part Number and Hardware Identification Sticker
The relay described by the sticker shown in Figure 7.1 is an SEL-321 Relay, serial
number 00001. The part number describes the relay configuration in a concise
manner. Some critical aspects of this part number are called out under the Power
Supply, Logic Input, and Secondary Input sections of the sticker.
The Power Supply specification shown in Figure 7.1 indicates that this relay is
equipped with a power supply that accepts 125 volts ac or dc. Other power supply
options include 24 volts dc, 48 volts dc, and 250 volts ac/dc. Refer to the sticker
attached to your relay to determine the magnitude of voltage you should apply to the
relay power supply input terminals. The voltage source should be capable of
providing 12 watts continuously at the rated voltage.
The Logic Input specification indicates that the relay logic inputs are rated to accept
125 volts dc. Other options include 24 volts dc, 48 volts dc, and 250 volts dc. To
assert a relay logic input, apply dc voltage to the relay input terminals. Refer to the
sticker attached to your relay to determine the magnitude of voltage you should
apply to the relay logic inputs. Approximately four milliamps of current flow when
rated voltage is applied to a relay logic input.
The Rotation specification indicates the expected power system phase rotation.
Figure 7.1 indicates that this relay is configured to accept ABC rotation. This is also
referred to as 123 or positive phase rotation by some utilities. Under nominal
conditions on a system with ABC rotation, B-phase voltage lags A-phase voltage by
120°, and C-phase voltage lags B-phase voltage by 120°.
The V/phase specification indicates the nominal ac voltage that the relay is designed
to measure. This voltage is specified from line to neutral and assumes a standard 4-
wire wye ac voltage connection. Figure 7.1 indicates that this relay is configured to
accept 67 volts ac, line to neutral. The relay measures other ac voltage magnitudes
accurately, as defined in
Section 2: Specifications
.
The Amps specification indicates the nominal ac current that the relay is designed to
measure. Figure 7.1 indicates that this relay is configured to accept 5 amps ac, per
phase. The relay measures other ac current magnitudes accurately, as defined in
Section 2: Specifications
.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......