Date Code 20011026
Specifications
2-3
SEL-321/321-1 Instruction Manual
Settings Zone
1 Zone
2 Zone
3 Zone
4
Zone
Reach Z1P Z2P Z3P Z4P
O/C
Supervisory
50PP1 50PP2 50PP3 50PP4
Outputs
Instantaneous M1P M2P M3P M4P
Time
Delayed
M2PT M3PT M4PT
Supporting Drawings: Figure 2.5 through Figure 2.9
G
ROUND
M
HO AND
Q
UADRILATERAL
D
ISTANCE
C
HARACTERISTICS
Each zone has separate phase and residual overcurrent supervision. The Zone 1 zero-sequence
compensation factor (k01) is independent from the compensation factor (k0) used for all other
zones.
Settings Zone
1 Zone
2 Zone
3 Zone
4
Mho
Reach
Z1MG Z2MG Z3MG Z4MG
Quad
Reactance
XG1 XG2 XG3 XG4
Quad
Resistance
RG1 RG2 RG3 RG4
Phase O/C Sup.
50L1
1
50L2 50L3 50L4
Res.
O/C
Sup. 50G1 50G2 50G3 50G4
k0
magnitude k01M k0M k0M k0M
k0
angle
k01A k0A k0A k0A
Outputs
Instantaneous Z1G Z2G Z3G Z4G
Time
Delayed
Z2GT Z3GT Z4GT
1
50L1 is also used for open pole logic and trip unlatch logic.
(The mho and quadrilateral characteristics share the same logical outputs Z1G - Z4G.)
Supporting Drawings: Figure 2.10 through Figure 2.18.
O
UT
-
OF
-S
TEP
(OOS) C
HARACTERISTICS
The rectangular impedance-plane characteristics use positive-sequence impedance and
overcurrent supervision.
When the impedance remains between Zones 5 and 6 longer than the OOS blocking delay
(OSBD), the relay logic prevents designated zones from tripping for up to two seconds.
Negative-sequence overcurrent conditions, detected by the 50Q1 - 50Q4 elements, remove OOS
blocking to permit tripping for unbalanced faults which may occur during swings.
The OOS characteristics do not affect ground-fault protection.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...