Date Code 20011026
Specifications
2-79
SEL-321/321-1 Instruction Manual
Figure 2.48: Trip Unlatch Logic for Phase A
D
ISTANCE
E
LEMENT
O
PERATING
T
IME
C
URVES AT
N
OMINAL
F
REQUENCY
Figure 2.49 shows operating times for the SEL-321 Relay distance elements. The diagrams show
operating times at each test point. Operating times include output contact closure time (for
standard and interrupting duty contact outputs).
For the distance element test, a fault was applied at a location representing a percentage of the
Zone 1 relay reach setting. Tests were performed for source impedance ratios (SIR) of 0.1, 1.0,
10.0, and 30.0. No pre-fault load current or fault resistance was included. Operating times are
the same for both 50 Hz and 60 Hz.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......