Date Code 20011026
Maintenance and Testing
7-5
SEL-321/321-1 Instruction Manual
When the upper line of the display reads:
PASSWORD: TAIL
press the EXIT button to enter Access Level 2. The relay briefly displays the note
Level 2
, then resumes the
EN
display.
Press the button labeled
SET
. The display shows:
SET GROUP
Press
SELECT
. Use the Down arrow button to enter the number 1, then press
SELECT
again.
Note:
The SEL-321 Relay includes six setting groups. While you are testing this
relay, it is important to change settings in the group that is active. If you
change settings in an inactive setting group, the relay performance will not
change. The relay is shipped with Setting Group 1 active. You may change
the active group by executing the
GROUP
command from the relay front
panel or from a terminal connected to a relay serial port. You must enter the
Breaker Access Level or Access Level 2 to change the active group.
Press the Down arrow button repeatedly, until the upper line of the display reads:
Misc Scheme Logic
Press
SELECT
. Press the Down arrow button repeatedly until the lower line of the
display reads:
TULO = 3
Press
SELECT
. Press the Up arrow button until the lower line of the display reads:
TULO = 1 *
Press
SELECT
. Press
EXIT
. Press
YES
to save the new settings.
Step 10.
Purpose: Test the fault locator.
Method: Test the fault locator using the voltages and currents in Table 7.1. These
voltages and currents were obtained for various locations and fault types assuming a
radial line with a source impedance of 0.2 times the total 100 mile line impedance.
Note:
To simplify this step, apply dc voltage to the IN1 input. The relay
recognizes the asserted input when applied dc voltage is approximately equal
to the Logic Input voltage rating shown on the relay identification sticker.
Input IN1 is programmed to monitor the breaker auxiliary contact, 52A.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......