![Schweitzer Engineering Laboratories SEL-321 Скачать руководство пользователя страница 133](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-321/sel-321_instruction-manual_1216711133.webp)
Date Code 20011026
Communications
3-23
SEL-321/321-1 Instruction Manual
SET G
Use the SET G command to configure relay inputs, set the front-panel time delay and the group
switching time delay. You assign inputs equal to any of the elements listed in Table 2.9. The
inputs are then dedicated to monitor those functions. Preceding an entry with (!) causes that input
to be treated as the inverse of the given entry. (For example, if connecting a 52B input, assign it
as !52A1 to cause it to be interpreted correctly.) The relay displays entered data and prompts for
a Y or N response. Enter Y to accept the settings.
IN1 - IN8 (IN1 - IN16 for two I/O board relays) and RMB1 - RMB8 define inputs. See
Section 2: Specifications
, Contact Inputs section, for a complete list of possible assignments for
the inputs. FP_TIMEOUT sets the time, in minutes, that the front-panel LCD display waits
before resetting. TGR defines the time, in seconds, the relay delays before switching groups.
ERESTART enables SEL-321-1 Relays to restart once on detection of a CR_RAM self-test
failure. Below are shown the default global settings (one I/O board version - 8 inputs):
=>>SET G <ENTER>
SET G <ENTER>
SET G <ENTER>
SET G <ENTER>
Input Contact 1 Assignment: IN1 = 52A1 ?
Input Contact 2 Assignment: IN2 = PT ?
Input Contact 3 Assignment: IN3 = CLOSE ?
Input Contact 4 Assignment: IN4 = PTXFR ?
Input Contact 5 Assignment: IN5 = NA ?
Input Contact 6 Assignment: IN6 = NA ?
Input Contact 7 Assignment: IN7 = NA ?
Input Contact 8 Assignment: IN8 = NA ?
Received Mirrored Bit 1: RMB1 = NA ?
Received Mirrored Bit 2: RMB2 = NA ?
Received Mirrored Bit 3: RMB3 = NA ?
Received Mirrored Bit 4: RMB4 = NA ?
Received Mirrored Bit 5: RMB5 = NA ?
Received Mirrored Bit 6: RMB6 = NA ?
Received Mirrored Bit 7: RMB7 = NA ?
Received Mirrored Bit 8: RMB8 = NA ?
Front Panel Timeout: (minutes) FP_TIMEOUT= 5 ?
Group Change Delay: (seconds) TGR = 5 ?
CR RAM Diagnostics Action: Restart Enable (Y/N) ERESTART=Y ?
IN1 = 52A1 IN2 = PT IN3 = CLOSE IN4 = PTXFR
IN5 = NA IN6 = NA IN7 = NA IN8 = NA
RMB1 = NA RMB2 = NA RMB3 = NA RMB4 = NA
RMB5 = NA RMB6 = NA RMB7 = NA RMB8 = NA
FP_TIMEOUT= 5 TGR = 5 ERESTART= Y
Save changes (Y/N) ? Y
Settings saved
=>>
To edit a specific global setting, enter that setting name after the SET G command. Type SET G
TGR to edit the TGR global setting. These settings may also be changed from the front panel.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......