7-54
Maintenance and Testing
Date Code 20011026
SEL-321/321-1 Instruction Manual
T
ROUBLESHOOTING
T
EST
R
ESULTS
The following information is intended to help you troubleshoot relay tests if the relay does not
perform as you expected.
Symptom:
What to check:
Incorrect Targets
•
Check the relay event report. Determine the asserted elements at
the instant the TRIP output was asserted.
•
Verify the ac connections by plotting currents and voltages from
event report data.
•
Verify the MTU, MTCS, and MTO settings to ensure the
appropriate elements are enabled to trip.
•
Verify the TULO setting. If a trip occurs and does not unlatch
following clearance of the fault, new faults do not generate new
targets. You may need to turn off ac current applied to the relay,
deassert 52A inputs, assert the External Trip Unlatch Input,
(EXTUL), or press the Target Reset button.
Incorrect Tripping
•
Check the current and voltage connections by applying small
signals to the connected current and voltage inputs. Trigger an
event report using the
TRIGGER
command. Plot the magnitude
and angle of measured currents and voltages.
•
Check the MTU, MTCS, and MTO settings to determine which
elements are enabled to trip.
•
Check the output logic equation settings to determine which outputs
are enabled to trip.
•
Check the settings of elements that are enabled to trip.
•
Check the settings of elements that supervise elements that are
enabled to trip.
Incorrect Distance
Element Characteristic
Shape
•
Check the voltage and current connections by applying small
signals to the connected current and voltage inputs. Trigger an
event report using the
TRIGGER
command. Plot the magnitude
and angle of measured currents and voltages.
•
Verify the distance element settings, including Zone 1 Extension
logic settings.
•
Verify the supervisory overcurrent element settings which apply to
the element under test: 50PP overcurrent elements supervise the
phase distance elements; 50G and 50L overcurrent elements
supervise the ground mho and quadrilateral distance elements.
•
Verify the negative-sequence directional element settings. 32QF
supervises forward-reaching phase and ground distance elements.
32QR supervises reverse-reaching phase and ground distance
elements.
•
Verify the Loss-of-Potential (LOP) logic and element settings. If
ELOP = Y, Y1, or Y2, the relay blocks operation of the distance
elements when LOP conditions are detected. If ELOP = Y, LOP
conditions are defined by the 50M, 59QL, 59PL, 50QF, and 50QR
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......