2-16
Specifications
Date Code 20011026
SEL-321/321-1 Instruction Manual
Pole Open Logic
This logic discriminates between a partially and fully-open line terminal. The Three-Pole Open
(3PO) condition asserts when all three phases of the line are disconnected. The Single-Pole
Open (SPO) condition asserts when one or two phases of the line remain energized.
A pole is open if the one (or two) 52A inputs associated with that phase are deasserted and if the
current in that phase is below pickup of the four overcurrent elements 50L1 - 50L4.
The output of this logic influences both phase and ground distance element operations. SPO and
3PO conditions have independent Time Delayed Dropout (TDDO) timers.
Timer Settings
Single-Pole Open Delay
SPOD
Stabilizing time delay after single-pole reclose.
Three-Pole Open Delay
3POD
Security time delay for dissimilar breaker pole
closing.
Trip-Open Pole Delay
TOPD
Any trip which occurs while TOPD is timing results
in a three-pole trip.
Outputs
Phase A Open
SPOA
Blocks 21AG, 21AB, and 21CA elements.
Phase B Open
SPOB
Blocks 21BG, 21AB, and 21BC elements.
Phase C Open
SPOC
Blocks 21CG, 21BC, and 21CA elements.
Single-Pole Open
SPO
Blocks all quadrilateral ground distance, clears
LOP, and asserts 32QF. Includes SPOD delay.
Three-Pole Open
3PO
Blocks all ground distance. Includes 3POD delay.
Trip-Open-Pole
TOP
TOPD timer is timing.
Supporting Drawing: Figure 2.39 and Figure 2.40.
Stub Protection Logic
The LOP condition can enable a definite-time overcurrent element to detect faults on bus
sections not having PTs or to provide backup protection if potentials are lost. The same 50M
overcurrent element used in the LOP logic serves as the fault detector for this logic. If ELOP =
N or N1, this logic is not enabled.
Timer Setting
Stub Protection Coord. Delay 50MFD
Define-time delay for 50MF.
Output
Stub Protection O/C Element 50MF
Asserts for faults during LOP conditions if 50M
asserted for 50MFD delay.
Supporting Drawing: Figure 2.41.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......