SEL-321/321-1 Instruction Manual
Mirrored Bits receive default state (string of 1s, 0s or Xs)
87654321
RXDFLT=00000X11
?
Use the RXDFLT setting to determine the default state the M
IRRORED
B
ITS
should use in place
of received data if an error condition is detected. The setting is a mask of 1s, 0s and/or Xs, for
RMB1 - RMB8, where X represents the most recently received valid value.
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB1PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB1DO= 1 ?
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB2PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB2DO= 1 ?
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB3PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB3DO= 1 ?
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB4PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB4DO= 1 ?
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB5PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB5DO= 1 ?
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB6PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB6DO= 1 ?
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB7PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB7DO= 1 ?
Mirrored Bits RMB_ Debounce PU time (1-8 msgs) RMB8PU= 1 ?
Mirrored Bits RMB_ Debounce DO time (1-8 msgs) RMB8DO= 1 ?
Supervise the transfer of received data (or default data) to RMB1-RMB8 with the M
IRRORED
B
ITS
pickup and dropout security counters. Set the pickup and dropout counters individually for
each bit.
For example, any received mirrored bit that is used for direct transfer tripping should have at
least a two received message pickup delay.
O
PERATION
Message Transmission
All messages are transmitted without idle bits between characters. Idle bits are allowed between
messages.
·
At 4800 baud, one message is transmitted each power system cycle.
·
At 9600 baud, one message is transmitted each 1/2 power system cycle.
Message Decoding and Integrity Checks
The relay will deassert a relay element bit, ROK for any of the following reasons:
·
Relay disabled.
·
M
IRRORED
B
ITS
not enabled.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......