Date Code 20011026
Communications
3-17
SEL-321/321-1 Instruction Manual
PULSE n t (SEL-321-1 Relay Only)
PULSE closes an output contact for testing or control purposes. Close any output contact for
0.125 - 1.0 seconds by executing the command in Access Level 2.
Execute the command PULSE n t, where n is the number of the contact you wish to close and t is
the time, in seconds, the contact remains closed. The contact remains closed for 1 second unless
you specify a shorter time. The example below closes output contact 3 for 0.5 seconds.
==>PULSE 3 0.5 <ENTER>
PULSE 3 0.5 <ENTER>
PULSE 3 0.5 <ENTER>
PULSE 3 0.5 <ENTER>
The Breaker Jumper (P7: J106) must be in place to pulse output contacts.
QUIT
QUIT returns control to Access Level 0 from Level 1, B, or 2. The command displays the relay
ID, date, and time of QUIT command execution.
Use this command when you finish communicating with the relay to prevent unauthorized access.
Control returns to Access Level 0 automatically after a settable interval (see TIMEOUT in Table
3.12) of no activity.
=>QUIT <ENTER>
QUIT <ENTER>
QUIT <ENTER>
QUIT <ENTER>
EXAMPLE: BUS B, BREAKER 3 Date: 02/01/93 Time: 15:15:32.161
=
RDMEM m (SEL-321-1 Relay Only)
The RDMEM command allows you to read the contents of selected relay memory areas. This
capability helps diagnose failure causes after a CR_RAM self-test failure. Use RDMEM RAM to
download the information stored in relay RAM (use this command before you remove power
from the relay). Use RDMEM EEPROM to download the contents of the relay nonvolatile
memory. Use RDMEM ALL to download all the corrupted information associated with a critical
RAM failure.
SET Commands
Configure the relay using four SET commands. Table 3.5 lists the various SET commands, their
formats and uses. Table 3.6 lists the editing keys that you use with all SET commands.
Following these tables is a detailed discussion of each command.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......