![Schweitzer Engineering Laboratories SEL-321 Скачать руководство пользователя страница 186](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-321/sel-321_instruction-manual_1216711186.webp)
5-10
Applications
Date Code 20011026
SEL-321/321-1 Instruction Manual
Out-of-Step Setting
Out-of-step tripping or blocking is not required for this application. The out-of-step elements are
disabled by setting EOOS = N.
EOOS = NNNN
- Relay Elements and Other Settings Affected
Relay Elements OSB, OST, X5ABC, X6ABC, and 50ABC.
Load-Encroachment Logic Setting
The relay uses a load-encroachment feature, which prevents operation of the three-phase
elements under high load conditions. This unique feature permits load to enter a predefined area
of the three-phase distance characteristic without causing a tripout.
The load-encroachment characteristic is defined by a load impedance setting in the forward and
reverse directions. Defined angle settings determine the load sector in the forward and reverse
direction.
The load-encroachment setting should be based upon maximum load flow conditions on the
protected line. The maximum short time load flow could be as high as 900 A with Line 5
removed. The maximum conductor current rating is 1200 amps. Assuming a 20% short time
overload factor, set the load impedance for 1440 A load. Nominal system voltage is 230 kV line-
to-line or 132.8 kV line-to-neutral. Assume a load angle range of ±30
°
. Both forward and
reverse load ranges are assumed to be the same.
Calculations: CTR = 200:1
PTR
=
2000:1
Iload =
1440
200
7 2
=
. A
secondary
Vbus =
138790
2000
66 4
=
. volts
secondary
Zload =
Vbus
Iload
=
=
66 4
7 2
9 22
.
.
.
Ω
secondary
ELE = YYYY
ZLF = 9.
9.
9.
9.22
22
22
22
ZLR = 9.22
9.22
9.22
9.22
PLAF = 30
30
30
30
NLAF = ----30
30
30
30
PLAR = 150
150
150
150
NLAR = 210
210
210
210
- Relay Elements and Other Settings Affected
Relay element ZLOAD.
Содержание SEL-321
Страница 4: ......
Страница 10: ......
Страница 12: ......
Страница 78: ...2 54 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 4 Logic Symbol Legend ...
Страница 87: ...Date Code 20011026 Specifications 2 63 SEL 321 321 1 Instruction Manual Figure 2 21 Load Encroachment Logic ...
Страница 94: ...2 70 Specifications Date Code 20011026 SEL 321 321 1 Instruction Manual Figure 2 29 Voltage Element Logic ...
Страница 162: ......
Страница 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Страница 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 264: ......
Страница 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Страница 266: ......
Страница 270: ......
Страница 358: ......
Страница 360: ......
Страница 362: ......
Страница 366: ......
Страница 370: ......
Страница 390: ......