62
Function:
If the current stage size of a stage fell below 75% of the original stage size, the stage alarm stage power
loss is triggered. The message
SPL
ALARM
and the stage number of the affected stage are signalled
alternatingly on the display and the contact of the alarm relay is activated.
If several stages are affected, only the lowest stage number of the affected stages is displayed.
The affected stage is switched off immediately and set to the stage type
“FOFF”. The stage is
locked for the control resp. manual operation. The stage type of the affected stage is blocked
and cannot be changed.
In order to reset the alarm and to activate the affected stages, the stages must be changed first. After
this, the stage size must be entered manually (SETUP/402) for each affected stage. The stage size for
these stages may now be set back to
“
AUTO
”. The stages may be switched again by the control resp.
in manual operation.
If no stage triggers the alarm anymore, the alarm is rese
t, provided that the function “Manual reset”
(SETUP/501 = NO) is deactivated. The alarm messages (display and alarm relay) are reset
automatically. The alarm relay is only reset, if no other alarm is active.
NOTE:
The monitoring of a stage only works, if the stage recognition for this stage is concluded or if
the stage size was entered manually.