INFO
(S
TAGE DATABASE
)
The switching cycles, the operating hours, the stage type / status, the current stage power and the stage
power with regard to the initial power (in %) are displayed in the
“INFO” menu for each stage. With these
data it is possible to draw conclusions about the condition of the system and the condition of the
individual stages.
NOTE:
The current stage size (in kVar) is only displayed, if the current transformer factor has been set
in the
“SETUP” menu.
The stage power with regard to the initial power (in %) is only displayed, if the stage recognition has
been completed or if the stage size was entered manually (see chapter Stage identification).
Select the
stage number
with
.
Select the stage
with .
Select the values
with
.
1.00
i
INFO
INFO
CC
25
kVar
Display of the stage size
is only active, if the CT has
been set, otherwise ----
1 2 3 3 4 max.
1
2
3
4
max.
1.00
i
MANUAL
INFO
98
%
Current stage value in % with
regard to the initial value.
Is only displayed, if the stage
recognition has been
completed or if the stage size
was entered manually.
Otherwise, only ---- is
displayed.
1
2
3
4
max.
1
2
3
4
max.
1.00
i
SETUP
INFO
OC
808
Switching cycles
of the stage
1
2
3
4
max.
1
2
3
4
max.
1.00
i
ALARM
Auto
Stage type / status:
AUTO: Stage is active
FOFF: Stage is deactivated
FON: Stage is always on
Flty: Stage is defective
1
2
3
4 max.
OPh
342
h
Operating hours
of the stage
1
2
3
4
max.
Jump upwards
to:
Display of the stage size