57
Set the temperature limit 1 in the SETUP/512.
Set the temperature limit 1 in the SETUP menu 512. The temperature limit 2 (SETUP/513) may
have to be increased, because the maximum setting range of the temperature limit 1 depends on
the set temperature limit 2:
TEMP1
max
= TEMP2
– 5K
Function:
Upon exceeding the temperature limit 1, the switching output fan is switched on. The status message
“
FAN
” is flashing on the display in the bottom line in the main menu. If the temperature in the switch
cabinet falls and if the value falls below the temperature limit 1 by 5 K, the switching output fan is
switched off again after 10 s. The status message
“
FAN
” is no longer shown on the display. A flapping
of the fan switching output is prevented by the temperature hysteresis of 5 K.
NOTE:
If the submenus
“INFO”, “MANUAL”, “SETUP” or “ALARM” are active, the status message
“FAN” is not displayed.
NOTE:
An active error message
Ai
/
abrt
suppresses the status message
“FAN”. Reset the error
message
Ai
/
abrt
by pressing the
(ESC) key for 3 s.