30
FIrST
SEtUP
YES
SETUP
Un
400
V SETUP
Setting of the nominal voltage:
Un = phase-phase voltage
. This value
is required for the monitoring of the
voltage tolerance. The stage sizes
saved in the stage database also refer
to the nominal voltage.
FIrST
SEtUP
NO
SETUP
Pt
1
SETUP
Entry of voltage transformer factor
(if no transformer is used, value = 1)
U-Con
U-LN
SETUP
U-LL
Setup of the type of voltage
measurement connection
(Phase-Neutral-Conductor-Voltage or
Phase-Phase-Voltage)
Ct
50
SETUP
Entry of current transformer factor
e.g. 250/5 = 50
Ai
YES
SETUP
“Yes”:
The
controller
performs an identification of
the phase (connection of
measuring
voltage
and
current) and of the occupied
and non-occupied switching
outputs (AUTO-INIT).
Out
AUTO
SETUP
Setting of the stage type for each
individual stage:
Select the stage number with buttons
“
”
or
“
”
.
Select the stage with button
“
”
.
AUTO
: Stage is active.
FOFF
: Stage is deactivated.
FON
: Stage is always on.
Flty
: Stage is defective (cannot be set)
PFC
On
SETUP
“ON” control ON,
“OFF” control OFF,
“HOLD” control is stopped