25
of the occupied and non-occupied
switching outputs (AUTO-INIT).
PFC
On
SETUP
“ON” control ON,
“OFF” control OFF,
“HOLD” control is stopped
CP1
1
SETUP
Target COS
ϕ 1 of the control
St
10
S SETUP
Switching time, waiting time between
switching the individual stages on and
off
OUt
SETUP
Setting of the stage type for each
individual stage:
Select the stage number with buttons
.
Select the stage with button .
AUTO
: Stage is active.
FOFF
: Stage is deactivated.
FON
: Stage is always on.
Flty
: Stage is defective (cannot be set)