Troubleshooting
Fault / alarm
Possible cause
Remedy
No notification on the display
Measuring / supply voltage is
missing
Check, if the connected
measuring voltage is in the
range of 90…550 V AC.
Check the correct
connection of the
measuring voltage and
correct it, if necessary.
Display notification
U
ALARM
Measuring voltage out of
tolerance
Check the measuring
voltage.
Check the setting of the
nominal voltage and the
voltage tolerance and
correct it, if necessary.
Check the set voltage
transformer factor.
Display notification
I lo
ALARM
Measuring current is too
small:
I < 5 mA (I is the actual
current which is measured by
the controller on the
secondary side of the
transformer)
Check the connection of the
current transformer, line
break possible.
Remove the short-circuit
jumper of the current
transformer.
The transmission ratio of
the used current
transformer is too large.
Display
I hi
ALARM
The current is greater than
permitted: I > 6 A
(I is the actual current which
is measured by the controller
on the secondary side of the
transformer)
Overload in the system.
Current transformer ratio is
too small
Check the
current transformer ratio of
the transformer, replace by
suitable transformer type, if
necessary.
Incorrect display of the voltages
Incorrect voltage transformer
ratio has been set
Connection identification of
the voltage measurement
identified as faulty
Check the setting of the
current transformer ratio in
the SETUP menu
(SETUP/100/Pt resp.
SETUP/203) and correct it
if necessary.
Check the setting
“Connection of voltage
measurement
”
(SETUP/205) and correct it
if necessary (depends on
the set nominal voltage).
Incorrect display of the current
Incorrect current transformer
ratio has been set.
Check the setting of the
current transformer ratio in
the SETUP menu
(SETUP/100/Ct resp.
SETUP/202) and correct it
if necessary.
The active power factor, active
and reactive power, missing
reactive power for the control
target are displayed incorrectly.
The automatic initialisation
has not been executed.
The automatic initialisation
was cancelled with error.
Start the automatic
initialisation
“SETUP/100/AI resp.
SETUP/207)
” in the SETUP
menu.